Voltage Drop Limits: What the 3% and 5% Figures Mean
The figures usually quoted are 3% for lighting and 5% for other uses. In the UK they come from BS 7671, Appendix 4, for an installation supplied from the public low-voltage network. They limit the voltage drop in the cable as a percentage of the supply voltage. They are not the same everywhere, and the limit that applies to a real job is the one in the project specification and the local wiring rules.
What each source says
- UK, BS 7671 (Appendix 4). 3% for lighting and 5% for other uses on an installation supplied from the public network. Higher figures of 6% and 8% are given for an installation with a private supply.
- IEC 60364-5-52. It gives informative guidance on voltage drop. The limit depends on the supply and on the country, so no single IEC figure is quoted here.
- US, NEC. The informational notes to sections 210.19 and 215.2 suggest 3% on a branch circuit and 5% for the feeder and branch circuit together. They are recommendations, not requirements.
Because the figures differ by supply, country and circuit type, the calculator offers 3% and 5% and lets you set your own limit.
How the percentage is worked out
The voltage drop in volts is divided by the supply voltage and multiplied by 100. For a single-phase 230 V circuit that is Vd ÷ 230 × 100. For three-phase, the drop between two lines is compared with the line-to-line voltage, such as 400 V. The guide on three-phase voltage drop shows the working.
Worked example: a 230 V circuit against 3% and 5%
A single-phase 230 V circuit carries 20 A over 30 m of 2.5 mm² copper at 70 °C, a power factor of 1. The cable's resistance at 70 °C is 7.41 × 1.1965 = 8.87 Ω/km, so the drop is 2 × 20 × 0.030 × 8.87 = 10.64 V.
| Check | Working | Result |
|---|---|---|
| Percentage | 10.64 ÷ 230 × 100 | 4.63% |
| Against 5% | 4.63 ≤ 5 | within the limit |
| Against 3% | 4.63 > 3 | over the limit |
| 3% of 230 V | 0.03 × 230 | 6.9 V allowed |
| Next size up, 4 mm² | 2 × 20 × 0.030 × 4.61 × 1.1965 | 6.62 V (2.88%) |
So the same cable passes a 5% limit and fails a 3% one, and the smallest size in the table that meets 3% is 4 mm². The size that meets the voltage drop is only one requirement: the cable must also carry the current safely, and the voltage drop calculator says so beside its answer.
Why a limit exists
Equipment is designed to work from a supply within a range of voltage, so the voltage lost in the cable has to leave enough at the load. A motor also needs enough voltage at its terminals while it starts, which this calculator does not check.
Common mistakes
- Mixing up circuit parts. A 3% figure may apply to one circuit, and a 5% figure to the whole run from the origin. The two drops add up, so a limit on the total is used up by every part of the run.
- Using the wrong reference voltage. Divide a three-phase line-to-line drop by the line-to-line voltage.
- Treating a recommendation as a rule. The NEC notes are informational. What binds a project is its specification and the wiring rules where it is built.
Checking a cable
Enter the circuit in the voltage drop calculator, pick 3%, 5% or your own limit, and it shows whether the drop is within it and the smallest size that is. The results are estimates: check the limit that applies to your job with the person responsible for the design.
Every number in this guide is reproduced by the calculator's automated tests. It has not been reviewed by a licensed engineer. See how guides are made.
Estimate only. Not a substitute for code-compliant design or review by a qualified engineer.