Voltage Drop Calculator

Check the voltage drop of a copper or aluminium cable for DC, single-phase and 3-phase loads, in mm² for UK (BS 7671) and IEC work or AWG for the NEC. Metric sizes follow IEC 60228, imperial sizes follow the NEC AWG and kcmil tables. Get the drop in volts and percent, a limit check and the smallest size that passes.

IEC 60364-5-52BS 7671NECEstimate only — verify with a qualified engineer

Cable & load

Supply & load
Cable

Metric uses IEC 60228 sizes (mm²), imperial uses NEC AWG and kcmil. The two are not equivalent. Length is the one-way route from supply to load.

R at 70 °C = 7.41 × (1 + 0.00393 × (70 − 20)) = 8.87 Ω/km

Vd = 2 × 20 A × 30 m × 8.87 Ω/km = 10.64 V (4.63%)

Cable details
Voltage drop
4.63 %

How it's calculated

Single-phase or DC
Vd = 2 × I × L × (R cos φ + X sin φ)
Three-phase (line-to-line)
Vd = √3 × I × L × (R cos φ + X sin φ)
Percentage drop
% = Vd / V × 100
Resistance at temperature
R_t = R_ref × [1 + α (t − t_ref)]
Parallel runs
R and X are divided by the number of runs
Voltage at the load
V_load = V − Vd
Cable loss
P = n × I² × R × L / runs, n = 2 or 3 conductors
mV/A/m (single-phase, PF 1)
mV/A/m = 2 × R (Ω/km)

I is the load current per phase, L the one-way length of the cable, R the conductor resistance per unit length at its operating temperature, X the reactance per unit length and φ the power-factor angle. The length is counted once: the factor 2 (or √3 for three-phase) already accounts for the return path. Resistance comes from the standard tables, which give it at 20 °C for IEC 60228 and at 75 °C for NEC Chapter 9 Table 8, and is corrected to the operating temperature with α = 0.00393 per °C for copper and 0.00403 for aluminium (0.00323 and 0.00330 at the NEC 75 °C reference). The limit check compares the drop with the percentage you choose, and the smallest size is the first size of the same material, in the same standard, whose drop is within it. If you enter power instead of current, the current comes from the power calculator relations.

Worked examples

CaseWorkingResult
Single-phase 230 V, 20 A, 30 m of 2.5 mm² copper at 70 °CR = 7.41 × (1 + 0.00393 × 50) = 8.87 Ω/km8.87 Ω/km
Its dropVd = 2 × 20 × 0.030 × 8.8710.64 V, 4.63%
Smallest size within 3% (6.9 V)4 mm²: 2 × 20 × 0.030 × 4.61 × 1.19654 mm², 6.62 V
Three-phase 400 V, 100 A, 50 m of 35 mm² copper, PF 0.85√3 × 100 × 0.050 × (0.627 × 0.85 + 0.08 × 0.527)4.98 V, 1.25%
120 V, 16 A, 100 ft of 12 AWG copper at 75 °C (NEC)2 × 16 × 100 × 1.98 / 10006.34 V, 5.28%
Three-phase 400 V, 150 A, 120 m of 95 mm² aluminium at 90 °C, PF 0.9R = 0.320 × 1.2821 = 0.410 Ω/km12.60 V, 3.15%

Assumptions

Frequently asked questions

What is an acceptable voltage drop?

In the UK, BS 7671 (Appendix 4) gives 3% for lighting and 5% for other uses for an installation supplied from the public low-voltage network, with higher figures (6% and 8%) allowed for a private supply. IEC 60364-5-52 also gives informative guidance, and the limit depends on the supply and the country. The NEC informational notes to 210.19 and 215.2 suggest 3% on a branch circuit and 5% for feeder plus branch circuit together, and are recommendations only. Motors need the voltage at their terminals during starting to stay above what the motor and the starter allow, which this calculator does not check.

What is the 3-phase voltage drop formula?

Vd = √3 × I × L × (R cos φ + X sin φ), with I the line current, L the one-way cable length and R and X the resistance and reactance per unit length. For a 3-phase voltage drop calculation, divide Vd by the line-to-line voltage and multiply by 100 for the percentage. Example: 100 A over 50 m of 35 mm² copper at 400 V and PF 0.85 is 4.98 V, or 1.25%.

What is the single-phase voltage drop formula?

Vd = 2 × I × L × (R cos φ + X sin φ). The factor 2 covers the live and neutral (or return) conductors. At power factor 1 this is the same as 2 × I × L × R, which is how the mV/A/m tables are built.

How do I calculate voltage drop for a cable?

Find the load current, enter the one-way length, the cable size and material, and the supply voltage. The calculator takes the resistance from the standard tables, corrects it to the operating temperature, and returns the drop in volts and percent with a check against the 3% or 5% limit. The worked examples above show the arithmetic step by step.

How do I reduce voltage drop?

Use a larger conductor, shorten the route, run conductors in parallel, use copper instead of aluminium, or use a higher supply voltage for the same power, because the same power then needs less current.

Why is the length one-way?

The formula already includes the return path: the factor 2 for DC and single-phase, and √3 for three-phase. Enter the distance from the supply to the load.

How does this compare with the mV/A/m tables?

For a load at unity power factor the drop in mV per ampere per metre is twice the resistance in Ω/km at the operating temperature: for 2.5 mm² copper at 70 °C that is about 17.7 mV/A/m, which agrees with the roughly 18 mV/A/m in the BS 7671 tables for a two-core cable. This calculator works from resistance and reactance, so it also covers other power factors, aluminium and parallel runs.

Can I use the smallest size shown?

Only if it also carries the current safely. The cable must meet current-carrying capacity (heating) limits, which depend on the installation method, grouping and ambient temperature, and be protected by a suitable device. Check it against the cable tables of your wiring code. The cable size calculator combines the voltage drop with a short-circuit check and tells you the rating the cable needs after derating.

How many amps for my load?

Choose "Power (kW)" under "Load given as", or use the power calculator to convert kW, kVA or motor hp to amps first.

Standards and references