Cable Size Calculator

Find the smallest copper or aluminium cable that keeps voltage drop within your limit and withstands a short circuit, and see the current rating your cable needs after derating. Metric sizes follow IEC 60228, imperial sizes follow the NEC AWG and kcmil tables. It does not contain ampacity tables: you check the rating in your own cable data.

IEC 60364-5-52BS 7671NECEstimate only — verify with a qualified engineer

Cable & load

Supply & load
Cable

The size is picked from 19 IEC 60228 (mm²) sizes. Length is the one-way route from supply to load. This tool does not hold current ratings: it tells you the rating the cable needs.

Required rating = 20 A (derating factor 1)

Voltage drop: 4 mm² gives 6.62 V (2.88%), within 3%

Conditions, fault and your cable rating

The derating factor combines ambient temperature, grouping and other factors from your wiring code (1 means none). Enter the rating your own cable table gives for the recommended size to check it against the load.

Cable size
4 mm²

How it's calculated

Voltage drop, single-phase or DC
Vd = 2 × I × L × (R cos φ + X sin φ)
Voltage drop, three-phase
Vd = √3 × I × L × (R cos φ + X sin φ)
Short-circuit withstand
S = I × √t / k
Rating the cable needs
I_required = I / C
Rating check
I_rated × C ≥ I
Conductor resistance at temperature
R_t = R_ref × [1 + α (t − t_ref)]

The cable has to pass three checks, and the recommended size is the smallest one that passes all of them. The voltage drop check is the same calculation as the voltage drop calculator: resistance at the operating temperature (70 °C for PVC, 90 °C for XLPE or EPR, or 75 °C for NEC PVC types) and reactance, over the one-way length. The short-circuit check uses the adiabatic equation: S is the minimum cross-section in mm², I the fault current in A, t the time the fault lasts in s and k a constant for the conductor and insulation. It is valid for fault times up to 5 s. The current rating check does not look anything up. It divides the load current by your derating factor C, the product of the ambient temperature, grouping and other factors from your wiring code, to give the tabulated rating the cable must have. If you enter the rating your own table gives for the recommended size, it checks that rating, multiplied by C, against the load. These k values are for live conductors, not for protective (earth) conductors, which start from a lower temperature and are not sized here.

k (A·√s/mm²)PVC, up to 300 mm²PVC, over 300 mm²XLPE / EPR
Copper115103143
Aluminium766894

The final conductor temperature is 160 °C for PVC (140 °C above 300 mm²) and 250 °C for XLPE and EPR. The values are the commonly published figures, and each can be derived from the heat capacity, resistivity and temperature coefficient of the metal using the adiabatic relation behind IEC 60949.

Worked examples

CaseWorkingResult
Single-phase 230 V, 20 A, 30 m, copper PVC 70 °C, 3% limit4 mm²: 2 × 20 × 0.030 × 4.61 × 1.19654 mm², 6.62 V (2.88%)
Rating it needsI_required = 20 / 120 A
The same load with a derating factor of 0.8I_required = 20 / 0.825 A, size unchanged
Fault 3000 A for 0.1 s, copper PVCS = 3000 × √0.1 / 1158.25 mm², so 10 mm²
Fault 3000 A for 0.1 s, copper XLPES = 3000 × √0.1 / 1436.63 mm², so 10 mm²
Fault 3000 A for 0.1 s, aluminium XLPES = 3000 × √0.1 / 9410.09 mm², so 16 mm²
Voltage drop and fault togetherlarger of 4 mm² and 10 mm²10 mm², decided by the fault
Your table gives 30 A, derating 0.8, load 20 A30 × 0.8 = 24 A, 24 − 20covers the load by 4 A (16.7%)

Assumptions

Frequently asked questions

How do I choose a cable size?

Find the load current, choose the cable's insulation and material, and then meet three limits together: the voltage drop at the full length, the current rating after derating, and the short-circuit withstand if the fault level is known. The largest size demanded by any of them is the one to use. This calculator does the first and last and tells you the second, so you can look it up.

What size cable for 20 A?

It depends on the length, the installation and the code, so there is no single answer. With a 230 V single-phase supply, 30 m of copper PVC cable and a 3% drop limit, the voltage drop alone needs 4 mm², and the cable must also be rated for at least 20 A in your installation (more after derating). Change the length and the answer changes.

What size cable for a 3-phase motor?

Set the system to three-phase, enter the line-to-line voltage, the current and the power factor, and the one-way length. For a motor, use the full-load current from the nameplate or from the power calculator. Starting current is not checked, so a long cable to a motor started direct-on-line needs a separate check.

What is a derating factor?

A multiplier below 1 that lowers a cable's tabulated rating for conditions worse than the table assumes, such as a high ambient temperature or several circuits bundled together. Your wiring code gives the factors. Enter the combined factor, and the calculator shows the rating the cable would need in the table: load current divided by the factor.

Is voltage drop or current rating the deciding factor?

Short cables are usually decided by the current rating, because the drop is small. Long cables are usually decided by the voltage drop, because the cable has to be larger than its rating requires to keep the volts up. Compare the "Voltage drop" size with the rating your table needs, and take the larger.

How do I find a cable's current rating?

From the datasheet for the cable you will buy, or from the current-carrying capacity tables in your wiring code (for example BS 7671 Appendix 4, IEC 60364-5-52 or NEC 310.16). The table is chosen by the cable type, how many loaded conductors it has and how it is installed.

Does it size protective (earth) conductors?

No. The short-circuit constants here are for live conductors, which start at their operating temperature. Protective conductors use different constants and rules.

Standards and references

This calculator estimates conductor size for voltage drop and short circuit. It does not size cables for current rating, protection or earthing, and it does not check any code requirement. Have the design checked by a qualified engineer.