Ohm's Law & Power Calculator

Solve Ohm's law from any two of voltage, current, resistance and power. Convert between amps, kW, kVA and kVAR for DC, single-phase and three-phase loads, including motors in kW or hp.

Ohm's lawIEC 60038NEC 430Estimate only — verify with a qualified engineer

Calculator

Ohm's law

I = V / R = 12 V / 4 Ω = 3 A

P = V² / R = (12 V)² / 4 Ω = 36 W

Current
3 A

How it's calculated

Ohm's law
V = I × R
Power from V and I
P = V × I
Power from I and R
P = I² × R
Power from V and R
P = V² / R
Single-phase AC
S = V × I, P = S × PF
Three-phase AC (V line-to-line)
S = √3 × V × I, P = S × PF
Power triangle
S² = P² + Q², Q = S × sin φ, φ = acos PF
Current from real power
I = P / (k × V × PF), k = 1 or √3
Motor input power
P in = P out / η

V is voltage, I current, R resistance, P real power in watts, S apparent power in volt-amperes, Q reactive power in var and PF the power factor. In Ohm's law mode, give any two of V, I, R and P and the other two follow from the three relations above: for example from I and P, V = P / I and R = P / I². For three-phase loads V is the voltage between two lines (400 V on a 400/230 V system) and the line-to-neutral voltage is V / √3. A motor's electrical input is its shaft power divided by its efficiency. One mechanical horsepower is 745.7 W and one metric horsepower (PS) is 735.5 W.

Worked examples

CaseWorkingResult
12 V across 4 ΩI = 12 / 4, P = 12² / 43 A, 36 W
Single-phase 230 V, 10 A, PF 0.8S = 230 × 10, P = S × 0.82.3 kVA, 1.84 kW
Its reactive powerQ = 2300 × √(1 − 0.8²)1.38 kvar, φ = 36.87°
Three-phase 400 V, 10 kW, PF 0.85S = 10 / 0.8511.76 kVA
Its currentI = 11 764.7 / (√3 × 400)16.98 A
7.5 kW motor, η 90%, PF 0.85, 400 V three-phaseP in = 7500 / 0.9 = 8333 W8.33 kW input
Its currentI = 8333 / 0.85 / (√3 × 400)14.15 A

Assumptions

Frequently asked questions

How many amps is 10 kW at 400 V three-phase?

With a power factor of 0.85 it is 16.98 A: I = 10 000 / (√3 × 400 × 0.85). At a power factor of 1 (resistive heating) it is 14.43 A. The lower the power factor, the more current the same kW needs.

How do I convert kW to kVA?

Divide by the power factor: kVA = kW / PF. A 10 kW load at PF 0.8 is 12.5 kVA. Choose "Real power" under "I know" and the calculator shows kVA, kvar and amps together.

How do I convert kW or hp to amps?

Pick the system and voltage, set the power factor, then choose "Real power" or "Motor output" and enter the kW or hp. For a motor, the shaft power is divided by the efficiency first, because the supply must deliver more than the shaft receives.

Why is a motor's current in the NEC table different from this result?

NEC (NFPA 70) Article 430 tells you to size motor branch-circuit conductors and protection from the full-load current tables, such as Table 430.250 for three-phase induction motors, not from a calculated or nameplate value. The table gives 14 A for a 10 hp, 460 V motor, while this calculator gives about 12 A for the same motor at 90% efficiency and PF 0.85. The table figure is deliberately conservative, so use it for code work.

Why does three-phase need less current than single-phase for the same power?

At the same voltage and power factor, three-phase current is 1/√3 (about 58%) of the single-phase current for the same real power.

What power factor should I assume if I do not know it?

Heaters and incandescent lamps are close to 1. Induction motors at full load are typically 0.8 to 0.9 and drop at light load. Check the nameplate or the supplier's data sheet before relying on a number.

Standards and references

This calculator estimates electrical quantities. It does not size cables, breakers or transformers, and it does not check any code requirement. Have the design checked by a qualified engineer.